Sensor-specific data | |
---|---|
Measuring Range | 10...400 cm/s |
Temperature of the medium, flow measurement | 0...125 °C** |
Temperature of the medium, temperature measurement | -25...150 °C |
Adjustable Range | 10...400 cm/s |
Medium | Water |
Measuring error | ? 2 % |
Response time in case of temperature jump | 10 s |
Environmental conditions | |
Ambient temperature | -25...80 °C |
Storage temperature | -25...80 °C |
Mechanical Strength | 100 bar |
EMC | DIN EN 61326-1 |
Shock resistance per DIN IEC 68-2-27 | 30 g / 11 ms |
Vibration resistance per DIN IEC 60068-2-6 | 5 g (10...2000 Hz) |
Electrical Data | |
Supply Voltage | 12...32 V DC |
Current Consumption (Ub = 24 V) | <{} 40 mA |
Switching Outputs | 2 |
Analog Outputs | 1 |
Analog Output | 0...10 V/4...20 mA |
Response Time | 1...5 s |
Switching Output/Switching Current | ± 100 mA |
Switching Output Voltage Drop | <{} 2 V |
Current Output Load Resistance | (Ub-Ubmin)/0,02A |
Load Current Voltage Output | ? 20 mA |
Short Circuit Protection | yes |
Reverse Polarity Protection | yes |
Protection Class | III |
Interface | IO-Link V1.1 |
Mechanical Data | |
Setting Method | IO-Link |
Housing Material | 1.4404 |
Material in contact with media | 1.4404 |
Degree of Protection | IP68/IP69K * |
Connection | M12 ? 1{} 4-pin |
Process Connection | G 1/2"{} CIP-capable |
Process Connection Length (PCL) | 75,5 mm |
Probe Length (PL) | 32 mm |
Output | |
Analog output switchable to flow or temperature | yes |
Switching output switchable to flow or temperature | yes |
Switchable to NC/NO | yes |
Configurable as PNP/NPN/Push-Pull | yes |
IO-Link | yes |
Connection Diagram | |
Dimensioned Picture | |
All dimensions in mm (1 mm = 0.03937 Inch) | |
Complementary Products | |
IO-Link Master | |
Software |
8 (029) 555-8-000 | |
8 (044) 555-8-000 | |
8 (017) 255-8-000 |